Tallinn

TRACTION SUBSTATION RECTIFIER FOR MAINLINE RAILWAY

TPRS Series
The rectifier is designed to convert alternating current into direct current at the traction substations of mainline railways.
Back to Catalog

Natural cooling ensures high reliability and overload capacity, maintenance is not required in the course of operation. Use of a common heatsink on two parallel diodes is a block minimizes quantity of buses and transitional contacts leads to reduced losses. Assembly includes a custom-made clamping mechanism allowing quick replacement of diodes without the need of neither removing the power equipment nor using special tools.

Design features:
  • In standard design the rectifier is manufactured to a 12-pulse current rectification circuit formed by subsequent connection of two bridges. The rectifier can be also assembled according to 6-pulse rectifier circuit.
  • Each diode is provided with the conductivity diagnostic circuit.
  • The rectifier is fitted with microprocessor protection and diagnostic system based on the TET ESTEL designed and manufactured controller and is equipped with operator’s control panel with a large LCD display.
  • The microprocessor control system equipped with an oscilloscope allows to perform continuous monitoring of the unit parameters, e.g. current, voltage, diode conductivity, temperature, waveform etc. Parameter values are saved in the unit’s internal memory and can be retrieved later for analysis. Control system generates alarm signals in case of faults, if they occur, and  forwards them according to the process protocol.
  • Designed to comply with RoHS and REACH requirements.
Rated output power range, kW5200- 10400
Rated output voltage, VDC3300
Rated output current range, А1600 - 3150
Allowed over-current time
*RMS value for every 8 hours should not exceed rated current value
** RMS value for every 30 minutes should not exceed rated current value
 @125 % – 900 s,
1 time per 2 hours*
AL
 @200 % – 10 s,
1 time per 2 min**
Rated input voltage range, V2610 (2*1305)
Input voltage frequency, Hz50 ; 60
Input voltage phases3
Rated input current range, А1285-2570
Coolingnatural air
Power factor (calculated), minimum0,95
Efficiency (calculated), minimum0,98
Protection class:
 
— power circuitIP21
— control systemIP54
Ambient temperature range, °Сfrom minus 25 to +45
Max. relative air humidity at +25°С, %98
Max. altitude above sea level, m2000