FCA-90S Series

Power units of FCA series are designed to supply aircrafts during preflight maintenance at the airport. They can also be used as a power unit of test benches, hangars and aircraft manufacturing plants.
FCA-90S is intended to supply all types of aircrafts with 400 Hz frequency and 3x115/200 VAC voltage during preflight preparation and technical maintenance.
Can be manufactured in both standard complete set and also by Client’s special requirements and adjustments.
• Smart operational TFT display
• Full diagnostic turn-up test
• Energy consumption metering system
• Modularity
• Maximum individual protection
• Innovative design
• Easy operation and maintenance
• Outgoing 400 Hz 3 phase sinusoidal voltage high quality
• High efficiency factor
• Energy consumption low level
| Output parameters: | |
| Rated output power, kVA | 90 |
| Rated output voltage phase/line, V | 3 x 115/200 |
| Output voltage frequency, Hz | 400 ± 0,001 |
| Output voltage regulation accuracy, %: | |
| — for the balanced load | ± 0,5 |
| — for 30 % unbalanced load | ± 0,5 |
| Total harmonic content, % | |
| — linear | ≤ 2 |
| — non-linear load | ≤ 2 |
| Voltage modulation, % | ≤ 1 |
| Phase symmetry, electrical degree: | |
| — for the balanced load | 120 ± 1 |
| — for 30 % unbalanced load | 120 ± 1 |
| Power factor | 0,8 – 1,0 |
| Range of load change, % | 0 – 100 |
| Voltage value change at 100 % load connection, % | ≤ 10 |
| Crest factor | 1,414 ± 0,03 |
| Permissible overload, %: | |
| — during 600 seconds | 150 |
| — during 30 seconds | 200 |
| — during 10 seconds | 250 |
| — during 5 seconds | 300 |
| — during 2 second | 400 |
| Input parameters: | |
| Supply main rated voltage, V | 3 x 400 (380) |
| Supply main permitted deviation, % | ± 15 |
| Supply main rated frequency, Hz | 50/60 |
| Supply main permitted frequency deviation, % | ± 10 |
| Power factor at 100% load | ≥0.97 |
| The total value of the harmonic distortion factor of the current at the input,% | ≤ 5 |
| Power consumption: | |
| — in standby mode with the switch off switch, W | ≤ 50 |
| — idling, kW | ≤ 1 |
| Efficiency in nominal mode,% | ≥ 96 |
| Power interruption | till 25 ms |
| Starting current | no, soft start |
| Additional data: | |
| Dimensions (WxHxD), mm | 600 х 1200 х 600 |
| Weight, kg | ≤ 365 |
| Ingress protection | IP55 |
| Max temperature conditions, ºС | + 56 |
| Min temperature conditions, ºС | - 40 |
| Aqustic noise level (1 m) | 55 dB |
| Humidity, % | 0-100 |